| The
Dust Detect 1000 monitors the flow of particulate emissions
through a filter in a dust collector or bag house. It
easily installs in the exhaust duct of your air filtration
system and can be used with several types of filtration
systems.
Features
-----------------
- Continuous monitoring of emissions through an air
filtration system
- Easy setup
- Emissions readings are averaged, not smoothed, to
eliminate false alarms
- Pre-warning indicator alerts you to potentially
hazardous situations
- Instantaneous alarm or one minute averaged readings
- 4-20 mA output available for use with your PLC
|
Specifications
|
| Enclosure: |
Die Cast Aluminum, FDA Approved Powder Coat |
| Power Requirement: |
115 VAC, 230 VAC Optional 60/50 Hz |
| Operating Temperature: |
-25° to +160°F (-32° to
+71°C) |
| Stack Temperature: |
+250°F (+107°C) |
| Process Connection: |
1 ¼" NPT |
| Conduit Connection: |
¾" NPT |
| Sensor Red: |
316 Stainless Steel
3, 6, & 12" Standard, 1.5 - 36" Custom Lengths Available |
| Output: |
Two SPDT 5A Relays (warning and alarm)
Optional 4-20 mA Signal |
| Alarm: |
Dual Alarm (alarm is 2x pre-alarm)
Switch Selectable For Instantaneous Or One Minute Average |
| Sensitivity: |
1mg/m (.0005 gr/SCF) |
|
 |